1. |
|
Perform normal tour checks and operations. |
|
2. |
|
Change compressor crankcase oil. |
|
3. |
|
Clean air intake filter.
|
|
4. |
|
Check air dryer, automatic condensate drains, and air tank for proper operation.
Clean condenser coils and cover grills.
|
|
5. |
|
Inspect belt alignment and condition. Adjust or replace belts as required. |
|
6. |
|
Check for corrosion and scale on water cooled units.
|
|
7. |
|
Clean heat exchange surfaces.
|
|
8. |
|
Check accuracy of gauges with calibrated test gauge.
|
|
9. |
|
On two stage compressor, check intermediate pressure. |
|
10. |
|
Test relief valves, replace if leaking or the relief range is incorrect. Do not
readjust safety relief valves in the field. |
|
11. |
|
Check operation of compressor unloaders, repair or replace if not loading and unloading
properly.
|
|
12. |
|
Check compressor suction and discharge valves for proper operation. Replace leaking
valves. |
|
13. |
|
Check cut in and cut out of compressor pressure controller, readjust if necessary
for proper air pressure requirements. Do not exceed ASME maximum tank pressure.
|
|
14. |
|
Check to make sure belt guard is installed prior to putting air compressor back
in service.
|
|
15. |
|
No pressure vessel is to have its hand hole or man hole covers removed unless the
vessel is at atmospheric pressure.
|